The working principle in four steps
- EvaporatorA fan draws outdoor air across a finned coil. The refrigerant inside is colder than the air, so it absorbs heat and evaporates into a gas.
- CompressorThe compressor squeezes the gas. Its pressure and temperature rise sharply, to well above the temperature you want in your water.
- Condenser (heat exchanger)The hot gas flows through a plate heat exchanger or tank coil. Water flowing past picks up the heat, and the refrigerant condenses to a liquid.
- Expansion valveAn electronic expansion valve drops the pressure and temperature of the liquid, ready to absorb heat from the air again.
Air to water heat pump system diagram
A typical domestic hot water system has four parts:
- Outdoor heat pump unit, mounted on the ground, a wall bracket or the roof.
- Water circulation pipes (insulated) between the heat pump and the tank, with a circulation pump (built-in on Pecol WHP-HW models).
- Hot water storage tank with temperature sensor, pressure and temperature relief valve, and backup element.
- Cold water supply with pressure reducing valve and one-way valve, and the hot water line to bathrooms and kitchen.
The controller watches the tank temperature. When it drops below the set point, the pump and compressor start; the water is heated by about 8°C each time it passes through the heat pump, until the tank reaches the set point.
How it heats domestic hot water
With domestic hot water, the system aims for 50–60°C in the tank. At a typical Malaysian air temperature of around 27°C and cold water at 28°C, the temperature lift is small, so the heat pump works at a very good COP. Pecol's DHW monoblock models are rated at COP 4.2–4.3 and the R32 DC inverter models at COP 4.7–4.95 for hot water.
COP at Malaysian ambient temperatures
COP (coefficient of performance) is heat output divided by electrical input. It goes up when the air is warm and the target water temperature is low, and goes down when the air is cold or the water must be very hot.
| Condition | Air temperature | Water temperature | Typical COP (Pecol R32 DC inverter) |
|---|---|---|---|
| Hot water, tropical | 20°C | 15→55°C | 4.73–4.95 |
| Low-temperature heating | 7°C | 30→35°C | 4.25–4.62 |
| Higher-temperature heating | 7°C | 47→55°C | 2.86–3.07 |
| Cold climate (EVI models) | -12°C | 41°C | about 2.7 |
Malaysian daytime air is usually warmer than these test points, so real hot water COP is often at the top of the range.
More on efficiency: heat pump COP and efficiency explained.
Can it cool as well as heat?
Yes. Reversible (multi-function) models can switch the cycle direction to make chilled water at 5–20°C for fan coil units, while still making hot water. See air to water heat pumps for cooling and heating.