How Does an Air to Water Heat Pump Work?

An air to water heat pump does not create heat; it moves it. Using the reverse Carnot cycle, it collects low-grade heat from the air and 'pumps' it up to a useful temperature in water. Here is the working principle in four steps.

Pecol air to water heat pump

The working principle in four steps

How a heat pump water heater works Refrigerant absorbs heat from outdoor air in the evaporator, the compressor raises its temperature, the condenser passes the heat into the water tank, and the expansion valve lowers the pressure so the cycle repeats. 1. Evaporator absorbs free heat from the air 2. Compressor raises temperature 3. Condenser releases heat into the hot water tank 4. Expansion valve lowers pressure low-pressure gas hot, high-pressure gas warm liquid cold liquid
The refrigeration cycle in reverse: about 1 kWh of electricity moves roughly 3–5 kWh of heat into your water.
  1. EvaporatorA fan draws outdoor air across a finned coil. The refrigerant inside is colder than the air, so it absorbs heat and evaporates into a gas.
  2. CompressorThe compressor squeezes the gas. Its pressure and temperature rise sharply, to well above the temperature you want in your water.
  3. Condenser (heat exchanger)The hot gas flows through a plate heat exchanger or tank coil. Water flowing past picks up the heat, and the refrigerant condenses to a liquid.
  4. Expansion valveAn electronic expansion valve drops the pressure and temperature of the liquid, ready to absorb heat from the air again.

Air to water heat pump system diagram

A typical domestic hot water system has four parts:

  1. Outdoor heat pump unit, mounted on the ground, a wall bracket or the roof.
  2. Water circulation pipes (insulated) between the heat pump and the tank, with a circulation pump (built-in on Pecol WHP-HW models).
  3. Hot water storage tank with temperature sensor, pressure and temperature relief valve, and backup element.
  4. Cold water supply with pressure reducing valve and one-way valve, and the hot water line to bathrooms and kitchen.

The controller watches the tank temperature. When it drops below the set point, the pump and compressor start; the water is heated by about 8°C each time it passes through the heat pump, until the tank reaches the set point.

How it heats domestic hot water

With domestic hot water, the system aims for 50–60°C in the tank. At a typical Malaysian air temperature of around 27°C and cold water at 28°C, the temperature lift is small, so the heat pump works at a very good COP. Pecol's DHW monoblock models are rated at COP 4.2–4.3 and the R32 DC inverter models at COP 4.7–4.95 for hot water.

COP at Malaysian ambient temperatures

COP (coefficient of performance) is heat output divided by electrical input. It goes up when the air is warm and the target water temperature is low, and goes down when the air is cold or the water must be very hot.

ConditionAir temperatureWater temperatureTypical COP (Pecol R32 DC inverter)
Hot water, tropical20°C15→55°C4.73–4.95
Low-temperature heating7°C30→35°C4.25–4.62
Higher-temperature heating7°C47→55°C2.86–3.07
Cold climate (EVI models)-12°C41°Cabout 2.7

Malaysian daytime air is usually warmer than these test points, so real hot water COP is often at the top of the range.

More on efficiency: heat pump COP and efficiency explained.

Can it cool as well as heat?

Yes. Reversible (multi-function) models can switch the cycle direction to make chilled water at 5–20°C for fan coil units, while still making hot water. See air to water heat pumps for cooling and heating.

Frequently asked questions

Where does an air to water heat pump get its heat from?
From the outdoor air. Even air at 20–35°C holds a lot of heat energy, which the refrigerant absorbs in the evaporator.
How hot can an air to water heat pump make water?
Standard models reach 55–60°C. Pecol's R134A high-temperature models reach 80°C.
Why is it more efficient than an electric heater?
An element converts 1 kWh of electricity into 1 kWh of heat. A heat pump uses 1 kWh to move 3–5 kWh of heat from the air.